Single Pole (SP) Tiny Trip Modular MCB – 6A to 32A

TINY TRIP MCB

Price on request

About this item

  • 6A single pole (SP) tiny trip MCB — modular, 1 module, C curve, 3000 A breaking capacity, 240 V AC.
  • Typically for a light or fan point, LED fittings or a small appliance, with 1 or 1.5 sq mm copper cable.
  • Protects the phase conductor; trips on overload and short circuit, resets with the toggle.
See full description

Buying options

Price on request

Quantity
Quote

Pick the options above, or leave them and we'll suggest the right one.

Product information

Single pole (SP) tiny trip MCB, 6A to 32A — modular mini MCB for switch plates, C curve, 3000 A breaking capacity, ISI-marked to IS/IEC 60898-1.

  • Mini MCB in modular switch form — 1 module wide, it fits a modular switch plate and box.
  • ISI-marked, made to IS/IEC 60898-1 (printed on the side of the unit).
  • 3000 A (3 kA) rated breaking capacity, marked on the front.
  • C curve (for example C 6 on the 6A unit) — rides through normal starting surges.
  • Rated 240 V AC, 50 Hz; protects the phase conductor of a single-phase point.
  • Trips on overload and short circuit and resets with the toggle — no fuse to replace.
  • Ratings 6A, 10A, 16A, 20A, 25A and 32A. Made in India.

A tiny trip MCB is a miniature circuit breaker made in the shape of a modular switch. It sits in the same plate and box as your switches and sockets, so an appliance point gets its own overload and short-circuit protection — and an on/off toggle — right at the switchboard. This single pole (SP) version is one module wide and switches the phase.

It is for per-point protection after the distribution board: its 3000 A (3 kA) breaking capacity is lower than the 10 kA of DIN-rail DB MCBs, so it supports the DB MCB rather than replacing it. It does not detect earth leakage — that needs an RCCB.

Which rating do I need

  • 6A — a light, fan or small-appliance point, on 1 or 1.5 sq mm cable.
  • 10A — TV, computer and small-appliance points or a geyser up to 2 kW, on 1.5 sq mm.
  • 16A — a power socket, a geyser up to 3 kW or a 1 to 1.5 ton AC, on 2.5 sq mm.
  • 20A — a 1.5 to 2 ton AC or a small single-phase pump, on 2.5 or 4 sq mm.
  • 25A — a 2 ton AC, an oven or induction cooktop, on 4 sq mm.
  • 32A — a 4 to 6 kW water heater or oven, on 6 sq mm.

Typical values with copper cable — your electrician should match the MCB to the load and the cable.

Where to use it

  • Socket points for a geyser, washing machine, microwave or refrigerator.
  • Adding overload and short-circuit protection to one point on a modular board.
  • Offices, shops and hotels — protection for a heavy appliance at its switchboard.

How to install

  1. Switch off the supply at the distribution board and confirm the point is dead.
  2. Connect the incoming and outgoing phase to the two terminals and take the neutral straight to the load — never switch the neutral with a single pole device.
  3. Clip the MCB into a free module of the plate, fix the plate to the box and switch on.

Electrical work should be done by a licensed electrician. For 240 V AC circuits only — not for solar panel or battery (DC) circuits.

Frequently asked questions

What is a tiny trip MCB?
A miniature circuit breaker built like a modular switch. It fits a modular switch plate, protects the point wired through it against overload and short circuit, and resets with its handle after a trip.
What does 3000A on the front mean?
The rated short-circuit breaking capacity: the MCB can safely interrupt a fault current of up to 3000 A (3 kA) — right for a point after the DB, whose own DIN-rail MCBs should be rated higher, such as 10 kA.
Single pole or double pole — which do I need?
Single pole switches and protects the phase only — fine for most socket, light and fan points. For AC, geyser and pump points where phase and neutral should both be disconnected, choose the double pole version.
Is it ISI marked?
Yes. The unit carries the ISI mark and IS/IEC 60898-1 on its side, as seen in the photos.
Does it protect against electric shock?
No. An MCB trips on overload and short circuit only. Protection against shock from earth leakage needs an RCCB of 30 mA or less in the distribution board.

Buy single pole tiny trip MCBs online from Electric Market, with delivery across India from our Chennai store. For site, contractor or bulk quantities, contact us for a quote.

SKUT10-9040-6ASP
ProductModular mini MCB (tiny trip), single pole
Poles1 (single pole, phase conductor)
Rated Current6A, 10A, 16A, 20A, 25A and 32A
Trip CurveC, marked with the rating (for example C 6)
Breaking Capacity3000 A (3 kA), as marked
Rated Voltage240 V AC, 50 Hz
StandardIS/IEC 60898-1, ISI marked (printed on the side)
Width1 module
MountingModular switch plate and box, like a switch module
ProtectionOverload and short circuit (not earth leakage)
Ampere Rating6A, 10A, 16A, 20A, 25A, 32A